Baid Power Services Pvt. Ltd.

Float Cum Boost chargers



Float- Boost Chargers

Float- Boost Chargers

Function:Float_Cum_Boost_Charger

POWER HOUSE FCBC are designed to supply continuous power to the DC load  and simultaneously charge the batteries connected. Input supply form 415 V. AC  3 Phase or 220 V. AC 1 Ph. is converted to regulate DC. The charger has two independent systems. Normally the DC power is supplied to the load by the Float Charger. It also supplies trickle current to the battery to keep it healthy. If the charging current under Float Mode exceeds a set level, Boost charger is switched ON. It supplies Quick charging current to the battery. On battery reaching the set value, the Boost Charger is switched OFF.

 Application:

Float/ Boost chargers are must in Power Substations, Generating Stations, Telephone Exchanges etc. for control / monitoring systems, tripping circuits and supplying DC power source.

Specifications:

Aux:                                         : 415V. AC ( 3 Phase) / 240 V (1 Phase)            
                                                   +/- 20 %/ +/- 10%,  50 Hz. +/- 3 Hz.
Out put                                     : 30 V, 48 V, 110 V and 220 V. DC supply 
Battery Type                            : Lead Acid / VRLA / PLANTA
Indications and instruments
                                                  : Indications for 3 phase mains supply
                                                  : Float / Boost section
                                                  : AC Volt meter with selector switch 
                                                  : DC Volt meter with selector switch and battery volt
                                                  : DC Amps meter for load
                                                  : DC Amps meter for Charging.
Protection  
                                                  : MCB for Mains incoming supply
                                                  : MCB for out put load
                                                  : Over load cut out by electronics circuit
                                                  : Over Voltage cut-out by electronics circuit
                                                  : Single phasing, under voltage for mains
Housing and enclosure:
                                                 : Heavy duty Sheet Steel Enclosure
                                                   Finished with Powder Coated paint.
Mounting                                 : Floor mounting
Operation                               : Auto/Manual
Control                                    : CC/ CV close loop
Rectifier                                  : Full wave half controlled bridge
Optional                                  : Fuse protection for each rectifier element
                                                : Fuse failure relay
                                                : DC Earth Fault Relay
                                                : Alarm Annunciation
                                                : Dual Float Charger option
                                                : Any other as per requirement.

 

 

Ordering Inffbormation:
Mains supply Voltage
Load voltage and current
Battery type, Voltage and current
Any optional equipments required

 

 

 

 

 

Download Catalogue 

 

Search

SHARE

AddThis Social Bookmark Button

Contact Us


Email:
Subject:
Message+ Contact Number:
How many eyes a typical person has?

You are here: Home FCBC and Power Plant

Power Services

33, Phears Lane, Kolkata  - 700073, West Bengal, India
Ph.: +91 033 22370508, +91 033 22360575
Fax: +91 033 22259090,email: info@indiapowerhouse.net

Baid Power Services Pvt. Ltd

152, Block-B, Lake Town, Kolkata - 700089, West Bengal, India
Ph: +91 033 25210322, Fax: +91 033 25343662
email: info@indiapowerhouse.net, Web: www.indiapowerhouse.com

 

"; urchinTracker();